sinee — 3.3.2Function and Wiring of Control Circuit Terminals

EM500 Open-Loop Vector Control Inverter User Manual See Figure 3–12 for control circuit terminal block. 24V M1 PLC COM Y1 Y2 COM GND M2 GND A+ A- RS485/CAN KeyBoard/ RS485/CAN RA RB RC Figure 3-12 Control Circuit Terminal Block Note: 1. Jump wires J9 and J10 of the terminal block are equipped by the manufacturer. No user is allowed to change them, or else inverter may not work normally. 2. S2 is VOID. M1 is analogy output ONLY for DC 0~10V. 3.3.2Function and Wiring of Control Circuit Terminals See Table 3–5 for functions of control circuit terminals. Table 3-5 Control Circuit Terminal Functions 48 1:CANH 2:CANL 3:KEY1 4:A- 5:A+ 6:KEY2 7:KEY3 8:GND RJ45-J5 8 1 RJ45-J3 8 1 Mode Terminal No.

Terminal Terminal Function 10V-GND 24V-COM +10V Power Offers a +10V power supply, maximum output current: 20mA. Supply Offers +24V power supply, generally used as a working power supply for numeric input or output terminal, or external device power supply. Maximum output current: 200mA. +24V Power Supply Auxiliary Power Supply PLC As factory default, it is connected to 24 V power supply. When driving numeric input terminal with an external power supply, disconnect it from 24V terminal and connect it to external power supply. Common Multi-function Input Terminal Analog Input AI1-GND Analog Input Input voltage range: DC 0 - 10 V