EM500 Open-Loop Vector Control Inverter User Manual 3.3.10 Control Circuit Cable and Screw Size  The length of cable for transmitting control signal should be limited to 50 m and its distance from power cable should be greater than 30 cm, in order to reduce interference and attenuation of control signal. Please use shielded twisted-pair cable when analog signal is input externally.  It’s recommended to use 0.5 - 1 mm 2 cable as the control circuit cable.  Terminal block of EM500 inverter shall be through control circuit connection terminal. Please use a cross screwdriver PH0 for installation with tightening torque of 0.5 N.m.

3.3.11Attentions for Control Circuit Wiring  Separate control circuit cable from other cable.  Separate cable of control circuit terminals EA, EB, EC, Y1 and Y2 from the cable of other control circuit terminals.  To prevent malfunctions caused by interference, use shielded twisted-pair cable for control circuit, with the wiring distance being less than 50m.  Wrap exposed shield net with insulating tape to prevent the shield net from contacting other signal cable and housing of device.  It’s not allowed to contact various ports or components without ESD measures. 3.3.12Standard Wiring of Control Circuit Standard wiring of control circuit of EM500 inverter is shown in Figure 3–22. 56