EM500 Open-Loop Vector Control Inverter User Manual previous/next non-factory default of the function code will be displayed accordingly. The lowest position of cursor will flash if current function code is permitted for change. The method of changing parameters is the same as that in the third level menu under all menu mode; after changing, press ENTER to save the change and enter the next non-factory default parameter.
For instance, if we set F00.03 as 1 and set F00.07 as 40.00 under the all menu mode, which are not factory defaults, then when entering the non-factory defaults mode, the first displayed value is F00.03; clockwise rotate digital potentiometer to switch to F00.07 and counter clockwise rotate digital potentiometer to back to F00.03. The following figure will be shown: Figure 4-7 Changing Function Parameters under Non-Factory Defaults Mode 4.3 Fault Monitoring When inverter is in fault state, press >> directly to switch among present fault type, fault output frequency, fault output current, fault output voltage, fault control mode and fault working time. 67