sinee — 6.2 Function Parameter Table

EM500 Open-Loop Vector Control Inverter User Manual 81 Field Weakening Factor 3 F01.17 Induction Motor Field Weakening Factor 4 10.00 - 100.00 % 72.00 〇 F01.18 Induction Motor Field Weakening Factor 5 10.00 - 100.00 % 70.00 〇 F01.19 Stator Resistor of Synchronous Motor 1 - 60000 (Motor Rated Power ≤ 75kW) 0.1 - 6000.0 (Motor Rated Power >75kW) mΩ Up To Specific Model 〇 F01.20 d-Shaft Inductance of Synchronous Motor 0.01 - 600.00 (Motor Rated Power ≤ 75kW) 0.001 - 60.000 (Motor Rated Power >75kW) mH Up To Specific Model 〇 F01.21 q-Shaft Inductance of Synchronous Motor 0.01 - 600.00 (Motor Rated Power ≤ 75kW) 0.001 - 60.000 (Motor Rated Power >75kW) mH Up To Specific Model 〇 F01.22 Counter Electromotive Force of Synchronous Motor 10.0 - 2000.0 (Counter Electromotive Force of Rated Rotation Speed) V Up To Specific Model 〇 F01.23 Initial Electric Angle of Synchronous Motor 0.0 - 359.9 (Synchronous motor enabled) 〇 F01.24 - F01.33 Not Used F01.34 Motor Parameter Autotuning 0:

No Autotuning 1: Stationary Autotuning of Induction Motor 2: Rotational Autotuning of Induction Motor 11: Stationary Autotuning of Synchronous Motor 12: Rotational Autotuning of Synchronous Motor 0 〇 F02 Input Terminal Function Group