EM600 High-Performance Vector Control Inverter User Manual 2.3 Considerations for Installation Site Caution 3. When carrying and transporting inverter, please hold its bottom. Only taking face panel would result in the risk of hitting your foot due to its dropping. 4. Please install inverter onto a metal panel or other non-flammable material panel. Installing it onto flammable materials may result in fire risk. 5. When at least two inverters are installed in the same control cabinet, please set cooling fan and maintain the air temperature of air inlet below 40 ℃ . Overheating would result in a fire or other accidents.
2.3.1 Installation Site Installation site shall be maintained to the following conditions: 1. Well-ventilated indoor place. 2. Ambient temperature: -10 C - 40 C. 3. Avoid high temperature and high moisture, humidity other liquid. 4. Do not install inverter onto wood or other flammable materials. 5. No direct sunlight. 6. No flammable or corrosive gas or liquid. 7. No dust, oily dust or floating fiber or metal particle. 8. Installation base shall be solid and free from vibration. 9. No electromagnetic interference and away from interference source. 2.3.2 Ambient Temperature For reliability purpose, please install inverter at a well-ventilated place.
A cooling fan or an air-conditioner shall be installed and ambient temperature shall be kept below 40 C, when inverter is installed in a closed box. 21 Model No. W W1/W2 H H1 H2 D D1 D2 d Frame EM600-315-3 801 680 1417 1383 1330 388 190 395 13 (d) EM600-355-3 EM600-400-3 EM600-450-3 1000 920 1800 1645 -- 600 520 450 17 (e) EM600-500-3 EM600-560-3 EM600-160-6 497 397 1107 1076 1036 340 285 348 13 (d) EM600-185-6 EM600-200-6 EM600-220-6