EM600 High-Performance Vector Control Inverter User Manual RS485 terminals of multiple inverters connect to host controller for communication:
A+ GND A- OFF A+ GND A- A- OFF A+ GND A- OFF A+ GND EM600 S1 EM600 S1 EM600 S1 EM600 S1 ON Figure 3-20 Wiring of Communication Interfaces of Multiple Inverters Connect to host controller for communication through RS485/RS232 converter EM600 A+ RS485/RS232 RS485/ RS232 通讯接口 Host Controller 上位机 S1 OFF A- RS232 Converter 转换器 RS232 Communica tion Interface GND Figure 3-21 Wiring of Communication Interface 3.3.9 Control Circuit Cable and Screw Size Length of cable for transmitting control signal shall be limited to 50 m and its distance from power cable shall be greater than 30 cm, in order to reduce interference and attenuation of control signal.
Please use shielded twisted-pair cable when analog signal is inputted externally. It’s recommended to use 0.5 - 1 mm 2 cable as control circuit cable. Terminal block of EM600 inverter shall be through control circuit connection terminal. Please use a PH0 cross screwdriver for installation with tightening torque of 0.5 N.m. 3.3.10 Attentions for Control Circuit Wiring Separate control circuit cable from other cable. Separate cable of control circuit terminals EA, EB, EC, Y1 and Y2 from cable of other control circuit terminals. To prevent malfunctions caused by interference, use shielded twisted-pair cable for control circuit, with the wiring distance less than 50m.