sinee — 9.2 Table of functional parameters

User Guide of EM730 Series Inverter 103 cy power consumption KWh 999.9 F19 Protection record group F19.00 Category of last protection 0: No protection E01: output short circuit protection E02: instantaneous overcurrent E04: steady-state overcurrent E05: Overvoltage E06: Undervoltage E07: input phase loss E08: output phase loss E09: inverter overload E10: inverter overheat protection E11: Parameter setting conflict E13: motor overload E14: External protection E15: inverter memory protection E16: communication abnormality E17: Temperature sensor abnormality E18: Abnormal disconnection of soft start relay E19: current detection circuit abnormality E20: Stall protection E21:

PID feedback disconnection E22: retention E24: parameter identification abnormality E25: retention E26: Load loss protection E27: up to the cumulative power-on time E28: up to the cumulative running time E43: Material cutoff protection E44: Cable protection E57: Overpressure in pipeline network E58: Under-pressure in pipeline network E76: Short-circuit protection to ground 0 × F19.01 Output frequency in protection 0.00 to upper frequency limit Hz 0.00 × F19.02 Output current in protection 0.00 to 650.00 (rated power of motor: ≤ 75 kW) 0.0 to 6500.0 (rated power of motor: > 75 kW) A 0.00 × F19.03 Bus voltage in protection 0 - 1200 V 0 × F19.04 Operating 0: not running 0 ×