User Guide of EM730 Series Inverter 66 27: clearing of regular running time 28: speed control/torque control switching 29: torque control prohibition 30: motor 1/motor 2 switching 31: resetting of simple PLC status (running from the first segment, with the running time cleared) 32: simple PLC time pause (keep running at current segment) 33: retention 34: counter input (≤250Hz) 35: high-speed count input (≤100kHz, only valid for X5) 36: count clearing 37: length counter input (≤250Hz) 38: High-speed length counting input (≤100kHz, only valid for X5) 39: Reset length (clear by meter) 40: Pulse input (≤100kHz, only valid for X5) 41: process PID pause 42: process PID integral pause 43:
PID parameter switching 44: PID positive/negative switching 45: stop and DC braking 46: DC braking at stop 47: immediate DC braking 48: fastest deceleration to stop 49: retention 50: external stop 51: switching of main frequency source to digital frequency setting 52: switching of main frequency source to AI1 53: Switching of main frequency source to AI2 54: retention 55: Switching of main frequency source to high-frequency pulse input 56: switching of main frequency source to communication setting 57: inverter enabling 68: Disable reversal 69: prohibit reversing 121: External material cutoff signal 122: Wiring detection signal 123: Brake reset terminal