sinee — 9.2 Table of functional parameters

User Guide of EM730 Series Inverter 90 F09.34 Multi-segment PID setting 3 0.0 to PID setting feedback range F09.03 0.0 ● F09.35 Upper limit of feedback voltage Lower limit of feedback voltage to 10.00 V 10.00 ● F09.36 Lower limit of feedback voltage 0.00 to upper limit of feedback voltage V 0.00 ● F09.37 Integral action option within set PID change time 0: Always calculate the integral term 1: Calculate the integral term after the F09.21 set time is reached 2: Calculate the integral term when the error is less than F09.38 0 Straight-2 ● F09.38 Integral within set PID change time Input deviation 0.00-100.00 % 0 ● F09.39 Wake-up option 0:

target pressure F09.01* coefficient of wake-up action point 1: Wake-up action point (F09.30) 0 〇 F09.40 Coefficient of wake-up action point 0.0-100.0 (100% corresponds to PID setting) % 90.0 ● F09.41 Pipeline network alarm overpressure 0.0 to pressure sensor range F09.03 % 90.0 ● F09.42 Overpressure protection time 0-3600 (0: invalid) bar 6 ● F09.43 PID reverse limit 0: no limit 1: limit 1 〇 F10 Communication function group F10.00 Local Modbus communicatio n address 1-247; 0: broadcast address 1 〇 F10.01 Baud rate of Modbus communicatio n 0:4800 1:9600 2:19200 3:38400 4:57600 5:115200 1 〇 F10.02 Modbus data 0: 1-8-N-1 (1 start bit + 8 data bits + 1 stop bit) 0 〇