sinee — EM730 User Manual (EN)

User Manual of EM730/EM730E Series Inverter 108 motor F14.20 d-axis inductance of synchronous motor 0.01~600.00 (rated power of motor: ≤ 75 kW) 0.001~60.000 (rated power of motor: > 75kW) mH Depending on the motor type 〇 F14.21 q-axis inductance of synchronous motor 0.01~600.00 (rated power of motor: ≤ 75 kW) 0.001~60.000 (rated power of motor: > 75kW) mH Depending on the motor type 〇 F14.22 Counter electromotive force of synchronous motor 10.0-2000.0 (counter electromotive force of rated speed) V Depending on the motor type 〇 F14.23 Initial electrical angle of synchronous motor 0.0-359.9 (valid for synchronous motor) 〇 F14.34 Motor parameter self-learning 00: No operation 01:

static self-learning of asynchronous motor 02: rotation self-learning of asynchronous motor 03: inertia self-learning of asynchronous motor 11: static self-learning of synchronous motor 12: rotary self-learning of synchronous motor 13: encoder self-learning of synchronous motor 00 〇 F14.35 Drive control mode of motor 2 0: V/F control (VVF) 1: Speed sensorless vector control (SVC) 0 〇 F14.36 Speed proportional gain ASR P1 _ 0.00-100.00 12.00 ● F14.37 Speed integral time constant ASR T1 _ 0.000-30.000 0.000: no integral s 0.200 ● F14.38 Speed proportional gain ASR P2 _ 0.00-100.00 8.00 ● F14.39 Speed integral time constant ASR T2 _ 0.000-30.000 0.000:

no integral s 0.300 ● F14.40 Switching frequency 1 0.00 to switching frequency 2 Hz 5.00 ●