User Manual of EM730/EM730E Series Inverter The magnetic saturation coefficient of the asynchronous motor is automatically set during the motor parameter self-identification. Users do not need to set it under normal circumstances. The function codes F01.19 to F01.23 are the parameters of the synchronous motor. They are usually unavailable to users. Please get them through motor parameter self-identification (F01.34). Before the motor parameter self-identification, be sure to set F01.00 to F01.08 correctly according to the actual situation. In particular, select the motor type (F01.00=2) correctly.
150 coefficient 4 of asynchronous motor F01.18 Magnetic saturation coefficient 5 of asynchronous motor 10.00 - 100.00 % 70.00 〇 Function Function code Default Parameter description Unit Attribute code name setting F01.19 Stator resistance of synchronous motor 1-60000 (rated power of motor: ≤75kW) 0.1 to 6000.0 (rated power of motor: > 75 kW) mΩ Model Confirm 〇 F01.20 d-axis inductance of synchronous motor 0.01 to 600.00 (rated power of motor: ≤ 75 kW) 0.001 to 60.000 (rated power of motor: > 75 kW) mH Model Confirm 〇 F01.21 q-axis inductance of synchronous motor 0.01 to 600.00 (rated power of motor: ≤ 75 kW) 0.001 to 60.000 (rated power of motor:
> 75 kW) mH Model Confirm 〇 F01.22 Counter electromotive force of synchronous motor 10.0-2000.0 (counter electromotive force of rated speed) V Model Confirm 〇 F01.23 Initial electrical angle of synchronous motor 0.0-359.9 (valid for synchronous motor) 0.0 〇 Function Default Function code name Parameter description Unit Attribute code setting F01.34 Motor parameter self-learning 0: No operation 1: static self-learning of 0 〇