User Manual of EM730/EM730E Series Inverter the gain by “k”, actual output by “Y” and standard output by “X”, the actual output is: Y=kX + b. 1. In order to meet the needs of different instruments or external devices, the full-scale voltage of M1 is actually 10.9V and the full-scale current is actually 22mA. 2. The default setting of M1 is 0.00-10.00V. 3. Where there are high precision requirements for the analog output during operation, test the no-load outputs of the terminals M1 with a multimeter first. be controlled by the corresponding bit of F03.31. 0 indicates no output and 1 indicates that there When the output functions of Y1 and R1 are set to “47:

PLC output”, the output result will is output. The output type of M1 is controlled by F03.34, and the corresponding short-circuit cap of the control panel M1 needs to be set correctly according to the output voltage or current: F03.34=0: output voltage 0-10V F03.34=1: output current 4-20mA F03.34=2: output current 0-20mA 7.5 Start/Stop Control Parameter Group of F04 Group F04.00=0: direct start 177 Function code Default t setting Function code name Parameter description Uni Attribute F03.31 Control logic options of PLC output terminal D7 D6 D5 D4 D3 D2 D1 D0 0*0 ● * * * * * R1 * Y1 0: no output 1:

Output Function Function code name Default Parameter description Unit Attribute code setting F03.34 Output type options of analog output M1 0: 0~10V 1: 4~20mA 2: 0~20mA 0 〇 Function Function code Unit Default Parameter description Attribute code name setting F04.00 Start-up method 0: direct start 1: start of speed tracking 0 〇