User Manual of EM730/EM730E Series Inverter Or, set F01.34=12 and press the RUN key. The inverter will start the rotary self-identification of the motor.  It takes about two minutes to complete the self-identification of the motor. Then the system will return to the initial power-on status from the “tune” interface.  If multiple motors are used in parallel, the rated power and rated current input of the motors should be the sum of power and current of these motors. If two motors are used alternately, the parameters of the motor 2 in the F14 group need to be set separately, and identified based on F14.34.

Chapter 6 Function Code Table 6.1 Description of Function Code Table The function codes of the EM730/EM730E series inverter (hereinafter referred to as the “function codes”) are divided into 24 groups in Table 6-2, and each group contains several function codes. Among them, the F18 group is a monitoring parameter group used to view the inverter status; the F19 group is a protection record group used to view the details of the last three protections; and other groups are parameter setting groups to meet different functional requirements.

Table 6-2 Introduction to Function Code Groups 64 F00 Basic function parameter group P66;P129 F01 Parameter group of motor 1 P69;P147 F02 Input terminal function group P70;P152 F03 Output terminal function group P74;P166 F04 Start/stop control parameter group P77;P177 F05 V/F control parameter group P79;P185 F06 Vector control parameter group P81;P191 F07 Protection function setting group P87;P199 F08 Multi-segment speed and simple PLC P89;P207 F09 PID function group P94;P217 F10 Communication function group P98;P231 F11 User-selected parameter group P99;P236 F12 Keyboard and display function group P101;P238 F13 Torque control parameter group P104;P243