User Manual of EM730/EM730E Series Inverter 6.2 Table of functional parameters 66 Function code settings before delivery, or values after parameter restoration (F12.14=1). This is mainly described by the following three categories. Number (e.g. Refer to each power segment. The function code is set to the current value by default. Default setting 50.00) Depending on The default setting of this function code varies based on the power segments. the motor type The default setting of this function code varies based on the power segments and batches. XXX Change attribute of the function code (permission and condition of change), as described below: Changeable in running:
The current function code can be changed in any status. ● Attribute Non-changeable in running: The current function code can be changed except in the running status. 〇 Read-only: The current function code cannot be changed in any status. × Function Default Function code name Parameter description Unit Attribute code setting F00 Basic function parameter group F00.00 Reserved F00.01 Drive control mode of motor 1 0: V/F control (VVF) 1: Speed sensorless vector control (SVC) 0 〇 F00.02 Options of command source 0: keyboard control (LOC/REM indicator: ON) 1: terminal control (LOC/REM indicator: OFF) 2: communication control (LOC/REM indicator:
flicker) 0 〇 F00.03 Options of terminal control mode 0: terminal RUN (running) and F/R (forward/reverse) 1: terminal RUN (forward) and F/R (reverse) 2: terminal RUN (forward), Xi (stop) and F/R (reverse) 3: terminal RUN (running), Xi (stop) and F/R (forward/reverse) 0 〇 F00.04 Options of main frequency source A 0: digital frequency setting F00.07 1:AI1 2:AI2 3: retention 4: retention 5: high frequency pulse input (X5) 6: main frequency communication setting 8 〇