sinee — EM730 User Manual (EN)

User Manual of EM730/EM730E Series Inverter 77 F03.34 Selection of analog output M1 type 0: 0~10V 1: 4~20mA 2: 0~20mA 0 〇 F04 Start/stop control parameter group F04.00 Start-up method 0: direct start 1: start of speed tracking 0 〇 F04.01 Start frequency 0.00 - 10.00 Hz 0.00 〇 F04.02 Start frequency hold time 0.00-60.00, 0.00 is invalid s 0.00 〇 F04.03 Starting current of DC braking 0.0~100.0 (100.0 = Rated current of motor) % 100.0 〇 F04.04 Starting time of DC braking 0.00~30.00 0.00: invalid s 0.00 〇 F04.06 Pre-excitatio n current 50.0-500.0 (100.0 = no-load current) % 100.0 〇 F04.07 Pre-excitatio n time 0.00 - 10.00 s 0.10 〇 F04.08 Speed tracking mode Ones place:

Tracking start frequency 0: maximum frequency 1: stop frequency 2: power frequency Tens place: Selection of search direction 0: search only in command direction 1: Search in the opposite direction if the speed cannot be found in the command direction 0 〇 F04.10 Deceleration time of speed tracking 0.1 - 20.0 s 2.0 〇 F04.11 Speed tracking current 30.0-150.0 (100.0 = rated current of inverter) % 50.0 〇 F04.12 Speed tracking compensatio n gain 0.00 - 10.00 1.00 〇