User Manual of EM730/EM730E Series Inverter 89 protection F07.22 Load loss detection level 0.0-100.0 % 20.0 ● F07.23 Load loss detection time 0.0 - 60.0 s 1.0 ● F07.24 Options of load loss protection action 0: trip protection, free stop 1: trip protection, stop according to stop mode 2: Continue to run, with DO status output 1 〇 F07.25 Motor overspeed detection level 0.0-50.0 (reference: maximum frequency F00.16) % 20.0 ● F07.26 Motor overspeed detection time 0.0-60.0, 0.0: disable motor overspeed protection s 1.0 ● F07.27 AVR function 0: Invalid 1: valid 2: automatic 1 〇 F07.28 Stall protection detection time 0.0-6000.0(0.0:

no stallprotection detection) s 0.0 〇 F07.29 Stall control intensity 0 - 100 % 20 〇 F07.30 Instantaneous stop/no-stop deceleration time 0.00 - 300.00 s 20.00 〇 F07.32 Action option 2 of protection E10 E13 E15 E16 * E19 E20 * 000 00000 〇 0: allow protection retry 1: disable protection retry F07.34 Action option 3 of protection * * * * * * E09 E17 *****00 〇 0: allow protection retry 1: disable protection retry F08 Multi-segment speed and simple PLC F08.00 Multi-segme nt speed 1 0.00 to maximum frequency F00.16 Hz 0.00 ● F08.01 Multi-segme nt speed 2 0.00 to maximum frequency F00.16 Hz 5.00 ●