User Manual of EM730/EM730E Series Inverter 97 options 2: sleep at lower frequency limit 3:
sleep with tube sealed F09.28 Sleep action point 0.00-100.00 (100.00 corresponds to the PID setting feedback range) % 100.00 ● F09.29 Sleep delay time 0.0 - 6500.0 s 0.0 ● F09.30 Wake-up action point 0.00-100.00 (100.00 corresponds to the PID setting feedback range) % 0.00 ● F09.31 Wake-up delay time 0.0 - 6500.0 s 0.0 ● F09.32 Multi-segme nt PID setting 1 0.0 to PID setting feedback range F09.03 0.0 ● F09.33 Multi-segme nt PID setting 2 0.0 to PID setting feedback range F09.03 0.0 ● F09.34 Multi-segme nt PID setting 3 0.0 to PID setting feedback range F09.03 0.0 ● F09.35 Upper limit of feedback voltage Lower limit of feedback voltage to 10.00 V 10.00 ● F09.36 Lower limit of feedback voltage 0.00 to upper limit of feedback voltage V 0.00 ● F09.37 Integral action option within set PID change time 0:
Always calculate the integral term 1: Calculate the integral term after the F09.21 set time is reached 2: Calculate the integral term when the error is less than F09.38 0 Straight-2 ● F09.38 Integral within set PID change time Input deviation 0.00-100.00 % 0 ● F09.39 Wake-up option 0: target pressure F09.01* coefficient of wake-up action point 1: Wake-up action point (F09.30) 0 〇 F09.40 Coefficient of wake-up 0.0-100.0 (100% corresponds to PID setting) % 90.0 ●