User’s Guide for EM760 series high-performance vector inverter KYP SPD 0.00Hz F12.03:Parameter Copy KYP SPD 0.00Hz Cur: OK Uploading Parameter Please Wait 1 1 0 100 1:Upload Parameter to Keypad ESC ESC Scope : 0~3 ESC ESC KYP SPD 0.00Hz Downloading Parameter Please Wait 1 2 100 2:Download Paremeter Scope : 0~3 ESC ESC ESC ESC It shall be particularly noted that: 1. No keyboard can be used for parameter downloading before it undergoes parameter uploading, as unknown parameters in the keyboard without parameter uploading may cause failure of an inverter by disturbing existing parameters in the inverter.
If a keyboard is used for parameter downloading without parameter uploading, it will prompt presence of no parameter in the keyboard, suggesting parameter downloading is 2. For parameter downloading to an inverter with a different version of CPUS software, the keyboard will unsuccessful; press ECS to exit; perform uploading again before downloading. prompt whether to continue downloading regardless of the different version; at this time, it is required to make clear whether parameter downloading is permitted between the two different versions. If yes, press ENTER key to execute the downloading; if no, press ESC to cancel the current operation.
Be cautioned that parameter uploading and downloading between two inverters with incompatible parameters are likely to cause operation failure of the inverters. 4.4 Run/Stop After setting the parameters, press the RUN key to enable the normal operation of the inverter, and the STOP key to stop the inverter. The M.K can be defined to free parking or to stopping inverter operation by changing the function code F12.00 to 5.
When function code F01.34 is set to corresponding self-learning mode, it is required to press RUN so that the inverter can enter corresponding parameter identification status; upon parameter identification, it will show "TUNE"; when identification is done, it will return to the original display, and the function code F01.34 will automatically change to 0. Upon rotation parameter identification by the inverter, the motor may rotate; in emergent cases, the user may press STOP to cancel identification. 33 KYP SPD 0.00Hz F12.03:Parameter Copy OK Cur: 0