5 PARAMETERS This chapter explains the function setting for use of this product. Always read the instructions before use. The following marks are used to indicate the controls. (Parameters without any mark are valid for all the controls.) 5.1 Parameter list 5.1.1 Parameter list (by parameter number) For simple variable-speed operation of the inverter, the initial values of the parameters may be used as they are. Set the necessary parameters to meet the load and operational specifications. Parameter setting, change, and check can be made on the operation panel. • The changing of the parameter settings may be restricted in some operating statuses.
Use Pr.77 Parameter write selection to change the setting. 72 5. PARAMETERS 5.1 Parameter list Mark Control method Applied motor V/F V/F control Three-phase induction motor GP MFVC General-purpose magnetic flux control NOTE Pr. Pr.
group Name Setting range Minimum setting increment Initial value Refer to page Customer setting Basic function 0 G000 Torque boost 0 to 30% 0.1% 6%*1 193 4%*1 3%*1 2%*1 1 H400 Maximum frequency 0 to 120 Hz 0.01 Hz 120 Hz 117 2 H401 Minimum frequency 0 to 120 Hz 0.01 Hz 0 Hz 117 3 G001 Base frequency 10 to 400 Hz 0.01 Hz 50 Hz 194 4 D301 Multi-speed setting (high speed) 0 to 400 Hz 0.01 Hz 50 Hz 109 5 D302 Multi-speed setting (middle speed) 0 to 400 Hz 0.01 Hz 30 Hz 109 6 D303 Multi-speed setting (low speed) 0 to 400 Hz 0.01 Hz 10 Hz 109 7 F010 Acceleration time 0 to 3600 s 0.1 s 5 s*2 93 10 s*2 15 s*2 8 F011 Deceleration time 0 to 3600 s 0.1 s 5 s*2 93 10 s*2 15 s*2 9 H000 Electronic thermal O/L relay 0 to 500 A 0.01 A Inverter rated current 112, 147 DC injection brake 10 G100 DC injection brake operation frequency 0 to 120 Hz 0.01 Hz 3 Hz 197 11 G101 DC injection brake operation time 0 to 10 s 0.1 s 0.5 s 197 12 G110 DC injection brake operation voltage 0 to 30% 0.1% 4%*3 197 2%*4 — 13 F102 Starting frequency 0 to 60 Hz 0.01 Hz 0.5 Hz 99