6. EtherNet/IP Settings 6.1.2. Connection Settings The connection settings of the FZ5 Sensor Controller are shown below. On the FZ5 Sensor Controller, set the connection type to Point to Point for both input and output. Set the Timeout Value so that it is longer than the FZ5 Sensor Controller’s measurement processing time. When the measurement interval is short, the measurement processing load is high, or command processing for operations such as scene group changing is time-consuming, the FZ5 Sensor Controller prioritizes measurement and control processing over communication processing. As a result, communication between an external device and occur.
In this case, set the communication error timeout time longer than the FZ5 Sensor the FZ5 Sensor Controller may be temporarily interrupted, and a communication error may Controller’s processing time. 9 Connection allocation Set value Connection I/O Type Consume Data From / Produce Data To Originator Device Input Tag Set D10100-[48 Byte] Connection Type Point to Point connection Output Tag Set D10000-[20 Byte] Connection Type Point to Point connection Target Device Output Tag Set Input 101-[48 Byte] _ Input Tag Set Output 100-[20 Byte] _ Packet Interval (RPI) 50.0 ms Timeout Value Packet interval (RPI) x 4