omron · 17 стр.
Руководство по эксплуатации GI-S - Настройка IP-адресов (EN)
Оригинальное название: GI PowerPoint
Похожие инструкции
Текст документа
GI-S series How to configure a software IP address with a DHCP server application SPD-1809139 Rev.B CONFIDENTIAL © OMRON Corporation 0 SPD-1809139 Rev.B CONFIDENTIAL © OMRON Corporation 0
Introduction When you add a GI-S to a network there are three ways to set the default IP address so you can program the I/O Block. 1) Rotary switches • Will set the IP address to 192.168.250.x. To do this set the rotary switches to 0xx where xx is the last octet in the IP address. 2) DHCP • Set the rotary switches to 000 or 400 (400 if you suspect the unit has an existing programmed IP address) • Cycle power to the GI-S and it will pick up an address from the switch DHCP (if enabled on the switch) • Use the switch software to determine what IP address the DHCP software on the switch gave to your device.
3) BOOTP-DHCP • This is a Rockwell Automation tool that lets you assign a specific IP address to a specific MAC address. • Set the rotary switches to 000 or 400 (400 if you suspect the unit has an exiting programmed IP address) Note: When you program the I/O block using Sysmac Studio you will set the device to a fixed IP address as part of the setup and the DHCP or BOOTP-DHCP servers will no longer be needed. There is no way to use Sysmac Studio to set the GI-S IP address without a Safety Controller being connected. Hence the need for DHCP to get the GI-S on the same network as the Safety Controller.
Preparation Necessary tools to use BOOTP-DHCP: BOOTP-DHCP server ver 3.01.00 (Rockwell Automation): BootP-DHCP allows you to assign a specific IP address to a specific MAC address. You can download here (Need to complete Account Registration): https://rockwellautomation.custhelp.com/app/answers/detail/a_id/19793 Sysmac Studio: Necessary to store software IP address into non-volatile memory. Wireshark: Only for troubleshooting (ex. In case you don’t know MAC address, you can’t remember stored IP address). https://www.wireshark.org/download.html
Preparation Network configuration: • PLC, target GI-S unit and Sysmac Studio PC must be in a network (accessible directly) and have same network ID. See two examples below. Using Port1: Using Port2: 192.168.250.1 DHCP server 192.168.1.100 DHCP server 192.168.250.100 DHCP client (to be 192.168.250.2) DHCP client (to be 192.168.1.2) NOTE: Refer user’s manual Z400-E1 6-4-1 Setting the IP Address - IP Addresses for detailed information network ID mechanism. 192.168.1.1