„ Precautions for CE Markings • Only basic insulation to meet the requirements of protection class I and over voltage category II is provided with control circuit terminals. Additional insulation may be necessary in the end product to conform to CE requirements. • For 400 V class Inverters, make sure to ground the supply neutral to conform to CE requirements. • For conformance to EMC directives, refer to section 3 in this document. For details, refer to the following document: Document No. EZZ008390 for English version „ Receiving • Do not install or operate any Inverter that is damaged or has missing parts. Failure to observe this caution may result in injury or equipment damage.
CAUTION „ Mounting 2 CAUTION Use 75 C copper wires or equivalent. Low voltage wires shall be wired with Class I Wiring. CAUTION • Lift the Inverter by the heatsink. When moving the Inverter, never lift it by the plastic case or the terminal covers. Otherwise, the main unit may fall and be damaged. • Mount the Inverter on nonflammable material (i.e., metal). Failure to observe this caution may result in a fire. • When mounting Inverters in an enclosure, install a fan or other cooling device to keep the intake air temperature below 122°F (45°C) for IP20 (open chassis type), or below 105°F(40°C) for NEMA1 (TYPE1). Overheating may cause a fire or damage the Inverter.
• The Inverter generates heat. For effective cooling, mount it vertically. Refer to the figure in Mounting Dimensions on section 3.