Quick Parameter List EN-12 Parameter No. Description Range Default n001 Parameter access: 1: Limited parameter access 4: Full parameter access 12: Factory parameter initialise 0 to 13 1 n002 Control mode selection: 0: V/F control mode 1: Vector control mode 0.1 0 n003 Run Command 0: Digital operator RUN, STOP/RESET 1: Control circuit terminal run/stop 2: Communications (MEMOBUS) 3: Communications (option) 0 to 3 0 n004 Frequency reference selection: 0: Digital operator (potentiometer) 1: Frequency reference 1 (n024) 2: Control circuit terminal (0 to 10V) 3: Control circuit terminal (4 to 20mA) 4: Control circuit terminal (0 to 20mA) 5: Control circuit terminal (Pulstrain reference) 6:
Communications (MEMOBUS) 7: Digital operator circuit (0 to 10V) 8: Digital operator circuit (4 to 20 mA) 9:
Communication (option) 0 to 9 1 n011 Maximum output frequency 50 to 400Hz 50Hz n012 Maximum output voltage 0.1 to 255V (200V class) 0.1 to 510V (400V class) 200 (200V class) 400 (400V class) n019 Acceleration time 1 0.0 to 6000sec 10 sec n020 Deceleration time 0.0 to 6000sec 10sec n024 Frequency reference 1 0.0 to 400Hz 6Hz n025-n031 Frequency reference 2-8 0.0 to 400Hz 0Hz n036 Motor rated current Depending on model 0 to 150% of inverter rated output current n050-n056 Multi-function input (S1-S7) 0 to 35 - n057 Multi-function output (MA-MB-MC) 0 to 21 1 n066 Multi-function analog output (AM-AC): 0: Output frequency (10V/Max, freq.) 1:
Output current (10V/Inverter rated current) 0 to 6 0 n080 Carrier frequency 1 to 4 (2.5 - 10kHz) 7 to 9 (Proportional to output freq.) Depending on model