omron — Electrical Connection

*1. The default settings are given for terminals S3 to S7. For a 3-wire sequence, the default settings are a 3-wire sequence for S5, multi- step speed setting 1 for S6 and multi-step speed setting 2 for S7. *2. Do not use this power supply for supplying any external equipment. *3. When driving a reactive load, such as a relay coil with DC power supply, always insert a flywheel diode as shown in Fig 6 Flywheel diode The rating of the flywheel diode must be at least as high as the circuit volt- age. External power: 30 VDC max. Coil 1 A max. Fig 6 Flywheel Diode Connection 1.

In Fig 4 the wiring of the digital inputs S1 to S7 is shown for the connection of contacts or NPN transis- tors (0V common and sinking mode). This is the default setting. For the connection of PNP transistors or for using a 24V external power supply, refer to Table 3 . 2. A DC reactor is an option only for Inverters of 18.5 kW or less. Remove the short circuit bar when con- necting a DC reactor. IMPORTANT IMPORTANT EN-10 Type No. Signal Name Function Signal Level Digital output signals M1 During run (1NO contact) Closed during Run Function selected by H2- 01 and H2-02 Relay contacts Contact capacity: 1 A max. at 250 VAC 1 A max.

at 30 VDC*3 M2 M3 Zero speed (1NO contact) CLOSED when output frequency at zero level (b2-01) or below M4 MA Fault output signal CLOSED across MA and MC during faults OPEN across MB and MC during faults MB MC analog output signals FM Output frequency Analog output fre- quency signal; 0 to 10 V; 10V=FMAX Function selected by H4-01 0 to +10 V max. ±5% 2 mA max. AC Analog common – AM Inverter output power Analog output power signal; 0 to 10V; 10V=max. appl. motor capacity Function selected by H4-04 RS-485/ 422 R+ MEMOBUS communications input For 2-wire RS-485, short R+ and S+ as well as R- and S-.

Differential input, PHC isolation R- S+ MEMOBUS communications output Differential input, PHC isolation S- IG Signal common – –