omron — Auto-Tuning (T1-oo)

5 Start Up ENGLISH For Auto-Tuning enter the Auto-Tuning menu and perform the steps shown in the fig- ure below. The number of name plate data to be entered depends on the selected type of Auto-Tuning. This example shows Rotational Auto-Tuning. Drive mode display Enter the Auto- Tuning Mode Select the tuning method Set up all name plate data The tuning start display appears During the tuning the DRV LED flashes After successful tuning “End” is displayed If Auto-Tuning can not be performed for some reason (no-load operation impossible etc.), then set up the maximum frequency and voltage in the E1- †† parameters and enter the motor data manually into the E2- †† parameters. NOTICE!

The Safe Disable inputs must be closed during Auto-Tuning. I67E-EN V1000 Quick Start Guide 19