omron — Operator Programing Errors

7 Troubleshooting ENGLISH An Operator Programming Error (OPE) occurs when an inapplicable parameter is set or an individual parameter setting is inappropriate. When an OPE error is dis- played, press the ENTER button to display U1-18 (OPE fault constant). This monitor will display the parameter that is causing the OPE error. ‹ Operator Programing Errors I67E-EN V1000 Quick Start Guide 29 LED Display ALM FLT Cause Controller Undervoltage  The drives controller power supply voltage is too low. DC Charge Circuit Fault  The charge circuit for the DC bus is broken. LED Operator Display Cause Corrective Action oPE01 Drive capacity and value set to o2-04 do not match.

Correct the value set to o2-04. oPE02 Parameters were set outside the allowable setting range. Set parameters to the proper values. oPE03 A contradictory setting is assigned to multi- function contact inputs H1-01 through to H1- 07. • The same function is assigned to two inputs (this excludes “External fault” and “Not used”) • Input functions which require the setting of other input functions were set alone. • Input functions that are not allowed to be used simultaneously have been set. • Fix any incorrect settings. • Refer to the instruction manual for more details. oPE05 • The run command source (b1-02) or fre- quency reference source (b1-01) is set to 3 but no option board is installed.

• The frequency reference source is set to pulse input but H6-01 is not 0. • Install the required option board. • Correct the values set to b1-01 and b1-02. oPE07 Settings to multi-function analog inputs H3- 02 and H3-10 and PID functions conflict. • H3-02 and H3-10 are set to the same value (this excludes settings “0” and “F”) • PID functions have been assigned to both analog inputs and the pulse input at the same time. • Fix any incorrect setting. • Refer to the instruction manual for more details. oPE08 A function has been set that cannot be used in the control mode selected (might appear after control mode change) • Fix any incorrect setting.

• Refer to the instruction manual for more details. oPE10 The V/f pattern setting is incorrect. • Check the V/f pattern settings. • Refer to the instruction manual for more details.