omron — Installation Environment

• Inspect the drive for damage. If the drive appears damaged upon receipt, contact your supplier. • Verify receipt of the correct model by checking the information on the nameplate. If you have received the wrong model contact your supplier. ‹ Installation Environment For optimum performance life of the drive, install the drive in an environment that meets the conditions listed below.

I67E-EN V1000 Quick Start Guide 7 SH 2 Mechanical Installation GLI ‹ Upon Receipt EN Environment Conditions Installation Area Indoors Ambient Temperature -10 °C to +40 °C (NEMA Type 1) -10 °C to +50 °C (Open-Chassis Type) When using an enclosure panel, install a cooling fan or air conditioner in the area to ensure that the air temperature inside the enclosure does not exceed the specified levels. Do not allow ice to develop on the drive. Humidity 95% RH or less and free of condensation Storage Temperature -20 °C to +60 °C Surrounding Area Install the drive in an area free from:

• oil mist and dust • metal shavings, oil, water or other foreign materials • radioactive materials • combustible materials (e.g., wood) • harmful gases and liquids • excessive vibration • chlorides • direct sunlight Altitude 1000 m or less Vibration 10 - 20 Hz at 9.8 m/s2, 20 - 55 Hz at 5.9 m/s2 Orientation Install the drive vertically to maintain maximum cooling effects.