Chapter 20 Network Configuration and Data Exchange (3) Select a node number in the # cell for the data supply node. The node number in the # cell for the data demanding node cannot be the same as the node number in the # cell for the data supply node. After the users select a node number, the PLC name corresponds to the node number will be appear in the Device Name cell for the node number. (4) Select a device type in the Register cell for the data supply node, and type an address in the Starting Address cell for the data supply node.
The device type selected in the Register cell for the data supply node does not have to be the same as the device type selected in the Register cell for the data demanding node. (5) Type a data length in the Size cell. A word is a unit. The maximum data length is 1900 words. After the users type a data length, the device ranges in the Range cells will change according to the data length typed. The users can create data exchange groups by following the steps described above.
The device range in the Range cell for a data demanding node cannot overlap the device range in the Range cell for another data demanding node whereas the device range in the Range cell for a data supply node can overlap the device range in the Range cell for another data supply node. In other words, different demanders can ask for the same data, but different data cannot be store in the same block. 20-63