ISPSoft User Manual 21.2 Permanent Data Backup There is flash memory in a DVP-EH2/DVP-EH2-L/DVP-EH3/DVP-EH3-L/DVP-SV/DVP-SV2 series PLC. The flash memory in a PLC is used to back up the data in the PLC. Please refer to manuals or documents for more information about the functions of flash memory. Users have to make sure that ISPSoft is connected to a PLC before they perform a data backup or a data restoration through ISPSoft. Click PLC Permanent Backup Setting on the Tools menu.
In the PLC Permanent Backup Setting window, the users have to select the PLC=>Flash option button or the Flash=>PLC option button in the Flash Memory Read/Write section , select contents which will be transferred, select the Enable option button or the Disable option button in the Warning Message section. (A data restoration is automatically performed when the flat battery in a PLC causes a data loss. If the Enable option button in the Warning Message section is selected, a warning message appears when a data restoration is automatically performed.) After the setting in the PLC Permanent Backup Setting window is complete, the users can click OK . 21-4