Chapter 21 Data Backup and Data Restoration 21.3.4 Command-line Instruction Execution CARD Utility supports instructions execution in command-line mode. The execution file (PLC CARD.exe) can be found in the installation directory of ISPSoft, which the default installation path would be set as C:\Program Files (x86)\Delta Industrial Automation\ISPSoft 3.10\PLC_CARD, then continue to follow the instructions below. Empty spaces are required to separate commands. /Lock and /UnLock cannot be used simultaneously as well as /C and /P. Commands and parameters are not case-sensitive; only password is set to be case-sensitive. Commands not required parameter inputs:
Commands required parameter inputs: 21−17 Commands Functions /RUN Run PLC. /Stop Stop PLC. /H Hide all message windows, but still have return codes as execution finished. /SaveOFF Disable the function of archiving returned codes. /? Display help messages. Other commands would be invalid while using this command. Commands Parameters Functions /PLC=P1 P1=PLC model type Specify the PLC model type for connection, e.g./PLC=AS332T. Supported model types:
AS300N,AS320T,AS320P,AS324MT,AS332T,AS332P。 AS218TX,AS218PX,AS218RX,AS228T,AS228P, AS228R,ES3。 /F=P1 P1=file name of DUP Download DUP file to PLC, e.g./F=test.dup /C=P1 P1=COM Port number Assign the COM Port number of PC, e.g./C=1 /Lock=P1, P2 P1=password,P2= the limited number of retries If the PLC is without password protection and no password is in the DUP file, users can set the password with this