Delta ISPSoft — 3.1.4.14 Function Card 1 Setting

Chapter 3 PLC System Configuration & Settings 3.1.4.14 Function Card 1 Setting The Function Card 1 Setting table is used for setting parameters of function card 1 in AS300 series CPU module, which is installed by inserting to the slot.  Users can select Auto in Card1 Detect mode box to detect the actual card model and setting or Manual to select the AS­-F232/ F422/ F485/F2AD/F2DA function card which need be configured in the Manual Select Card box.  For the setting of parameters in AS­-F232/ F422/ F485.  Users can set F2AD to receive the signal of 0~10V or 4~20mA in F2AD Analog Input Mode box and set F2AD to send the signal of 0~10V or 4~20mA in F2DA Analog Output Mode box.