Delta ISPSoft — 3.3.2.2 CPU Basic Parameter: System

ISPSoft User Manual  Error Log Location If the PLC option button is selected, error logs will be stored in the special data registers in the CPU modules. If the PLC and PLC CARD option button is selected, error logs will be stored not only in the CPU module, but also in the memory card. Twenty error logs at most can be stored in an AH500 series CPU module. If there are more than twenty error logs, the oldest error log will be overwritten by the latest error log. However, if the PLC and PLC CARD option button is selected, and there are more than twenty error logs, the oldest error log will be backed up in the memory card before the oldest error log is overwritten.

 CPU Operation at Program Error & CPU Operation at Bus Fault If an error occurs, the status of the CPU may change. The status of the CPU depends on an error code generated. Users can define the status of the CPU module for some errors. They can select the Stop option button or the Continue option button in the CPU Operation at Program Error section, select the Stop option button or the Continue option button in the CPU Operation at Bus Fault section, and download the parameters to the CPU module. Please refer to operation manuals or related technical documents for more information.  Remote Reset If the Enable checkbox is selected, the CPU module can be reset through a remote system.

After users select the Enable checkbox, and download the parameter to the CPU module, they can click Format PLC Memory… on the PLC menu, and select the Reset PLC Memory (Factory Setting) option button in the Format PLC Memory window. 3-166