ISPSoft User Manual 3.6.2.9 Options - Filtration Time Zone of Input Points The setting page for DVPxxMC Filtration Time Zone of Input Points and updates IO along. Enable the filtration time of input points -I0~I7 The input points to filter the short pulse signals via filtration is set between -I0~I7. This can increase filtration rate and reduce signal interference, input signal tremble or external interference. Users can select enable or disable IO filter via the drop-down menu. Enable the filtration time of input points -I10~I17 The input points to filter the short pulse signals via filtration is set between-I10~I17.
This can increase filtration rate and reduce signal interference, input signal tremble or external interference. Users can select enable or disable IO filter via the drop-down menu. Filtration Time Factor of I0~I7 The I0~I7 time factor of filtration is set between 0~255. The filtration time: t=31us * (time factor of filtration), the filtration time is a multiple of 31us and the default value of time factor is set to 0. Filtration Time Factor I10~I13 The I10~I13 time factor of filtration is set between 0~255. The filtration time: t=31us * (time factor of filtration), the filtration time is a multiple of 31us and the default value of time factor is set to 0.
Filtration Time Factor I14~I17 The I14~I17 time factor of filtration is set between 0~255. The filtration time: t=31us * (time factor of filtration), the filtration time is a multiple of 31us and the default value of time factor is set to 0. 3-228