Delta ISPSoft — 6.2.6 Downloading the Initial Values of the Symbols

Chapter 6 Symbol Variables Specific models with the latest hardware versions support three new initialization processes, Stop  Run initializing retentive symbols, Stop  Run initializing non-retentive symbols and Initializing retentive symbols. Please refer to section 3.1.5 and download the configured initialization setting to the PLC device before downloading the project. ISPSoft would detect automatically whether the connected device supports the new initialization processes. If yes, the option “Symbol Initial Value(Active when STOP  RUN)” would not able to be unselected as shown below.

After the initial values download is complete, go to PLC (P) > Initial value setting (I) > Initial retentive symbols must be checked (R), then confirm on the initialization action, as well as the normal connection between ISPSoft and the CPU 6-35 Model Types Hardware Ver. Max. Capacity of Initial Values Table AH5x1-RS2 1.05.00 80K Bytes AH5x1-EN 2.03.00 80K Bytes AH560-EN2 1.02.00 80K Bytes AS 1.06.60 20K Bytes ES3 0.40.10 20K Bytes AHxxEMC 2.03 80K Bytes MH/MP 1.00.00 80K Bytes AS Simulator 1.06.60 20K Bytes