5.6 H: Terminal Functions Setting 1A: During Reverse The During Reverse digital output will close whenever the drive is turning the motor in the reverse direction. Output frequency FWD Run command REV Run command During Reverse time Figure 5.25 Reverse Direction Output Example Time Chart Setting 1E: Restart Enabled The Restart Enabled output will be closed once the fault restart function becomes active and will remain closed until a successful restart is accomplished or the number of Auto Restart attempts as specified by L5-01 is reached. Refer to L5: Fault Restart on page 107 for details on automatic fault restart. Setting 3C:
LOCAL/REMOTE Status Output terminal closes while the drive is set for LOCAL and opens when in REMOTE. Setting 3D: During Speed Search Output terminal closes while Speed Search is being performed. Setting 100 to 13D: Reverse Switching for Functions 0 to 3D These settings reverse the switching status of the specified function. Set as 1 , where the last two digits specify the setting number of the function to be reversed. Examples: • To reverse the output for “8: During Baseblock”, set “108”. • To reverse the output for “3C: Run command” set “13C”. u H3: Analog Input Terminal A1 Settings These parameters adjust the signal level and characteristics of the analog frequency reference input A1.
n H3-01: Terminal A1 Signal Level Selection Selects the input signal level for analog input A1. Setting 0: 0 to 10 Vdc with Limit The input level is 0 to 10 Vdc. Negative input values will be limited to 0. Example: Terminal A1 is set to supply the frequency reference, and the bias (H3-04) is set to -100%. The frequency reference can be set from 0 to 100% with an analog input of 5 to 10 V. The frequency reference will be zero when the analog input is between 0 and 5 V. 98 SIEP C710606 33A OYMC AC Drive – J1000 User Manual Status Description Open Motor is driven in the forward direction or stopped. Closed Motor is driven in reverse. OFF ON Status Description Open REMOTE:
The selected external reference (b1-01/02 or MEMOBUS/Modbus) is used as frequency reference and Run command source Closed LOCAL: The digital operator is used as frequency reference and Run command source No. Name Setting Range Default H3-01 Terminal A1 Signal Level Selection 0 to 3 0