5.7 L: Protection Functions Setting 1: Enabled When the soft CLA current level is reached, the drive reduces the output voltage in order to reduce the current. If the current level drops below the Software CLA level, then normal operation will continue. n L8-35: Installation Method Selection Selects the type of installation and changes the drive overload (oL2) limits accordingly. Note: 1. This parameter is not reset when the drive is initialized. 2. The value is preset to the appropriate value when the drive is shipped. Change the value only when using Side-by-Side installation or when mounting a standard drive with the heatsink outside the cabinet. Setting 0:
IP20/Open-Chassis Drive Must be selected if an IP20/Open-Chassis drive is installed with minimal 30 mm space to the next drive or a cabinet wall. Setting 1: Side-by-Side Mounting Must be selected if drives are Side-by-Side mounted with a minimum space of 2 mm. Setting 2: NEMA Type 1 Drive Must be selected if the drive has a NEMA Type 1 enclosure. Setting 3: Finless Drive or External Heatsink Installation Must be selected for finless drives or if a standard drive is mounted with the heatsink outside the cabinet. n L8-38: Carrier Frequency Reduction Selection The drive can reduce the carrier frequency when the output current exceeds a certain level.
This temporarily increases the overload capability (oL2 detection) and the drive can run through transient load peaks without tripping. L8-38 selects the operation of the carrier frequency reduction function. Setting 0: Disabled No carrier frequency reduction at high current. Setting 1: Enabled for Output Frequencies below 6 Hz The carrier frequency is reduced at speeds below 6 Hz when the current exceeds 100% of the drive rated current. The drive returns to its normal carrier frequency when the current falls below 88% or the output frequency exceeds 7 Hz. Setting 2: Enabled for Entire Frequency Range The carrier frequency is reduced at the following speeds:
• Below 6 Hz when the current exceeds 100% of the drive rated current. • Above 7 Hz when the current exceeds 112% of the drive rated current. The drive uses the delay time of 0.5 s and a hysteresis of 12% when switching the carrier frequency back to the set value. 110 SIEP C710606 33A OYMC AC Drive – J1000 User Manual No. Name Setting Range Default L8-35 Installation Method Selection 0 to 3 0 No. Name Setting Range Default L8-38 Carrier Frequency Reduction Selection 0 to 2 Determined by o2-04