B.2 Parameter Table Default setting value is dependent on parameter C6-02, Carrier Frequency Selection. Parameter can be changed during run. Default setting value is dependent on parameter o2-04, Drive Model Selection and C6-01, Drive Duty Selection. u d: References Reference parameters are used to set the various frequency reference values during operation. Parameter List B SIEP C710606 33A OYMC AC Drive – J1000 User Manual 173 No. Name Description Range Def. Mode Addr. Hex Pg. C6-02 Carrier Frequency Selection Selects the carrier frequency 1 : 2.0 kHz 2 : 5.0 kHz 3 : 8.0 kHz 4 : 10.0 kHz 5 : 12.5 kHz 6 : 15.0 kHz 7 : Swing PWM 8 to E : No setting possible F :

User defined (determined by C6-03 through C6-05) 1 to F S 224 79 C6-03 Carrier Frequency Upper Limit C6-03 and C6-04 set upper and lower limits for the carrier frequency. carrier frequency C6-03 C6-04 output frequency × (C6-05) × K output E1-04 frequency max output frequency The coefficient K depends on C6-03: C6-03 ≥ 10.0 kHz: K = 3 10.0 kHz > C6-03 ≥ 5.0 kHz: K = 2 5.0 kHz > C6-03: K = 1 When C6-05 ≤ 6, C6-04 is disabled (makes the carrier frequency C6-03 value). 1.0 to 15.0 O 225 80 C6-04 Carrier Frequency Lower Limit 1.0 to 15.0 O 226 80 C6-05 Carrier Frequency Proportional Gain Sets the relationship of output frequency to carrier frequency when C6-02 = F. 00 to 99 O 227 80 No.

Name Description Range Def. Mode Addr. Hex Pg. d1: Frequency Reference Use d1 parameters to configure the drive frequency reference. d1-01 Frequency Reference 1 Frequency reference 0.00 to 400.00 Hz 0.00 Hz S 280 82 d1-02 Frequency Reference 2 Frequency reference when digital input "Multi-Step Speed Reference 1" (H1- = 3) is on. 0.00 Hz S 281 82 d1-03 Frequency Reference 3 Frequency reference when digital input "Multi-Step Speed Reference 2” (H1- = 4) is on. 0.00 Hz S 282 82 d1-04 Frequency Reference 4 Frequency reference when digital inputs "Multi-Step Speed Reference 1, 2" (H1- = 3 and 4) are on.

0.00 Hz S 283 82 d1-05 Frequency Reference 5 Frequency reference when digital input "Multi-Step Speed Reference 3" (H1- = 5) is on. 0.00 Hz O 284 82 d1-06 Frequency Reference 6 Frequency reference when digital inputs "Multi-Step Speed Reference 1, 3 " (H1- = 3 and 5) are on. 0.00 Hz O 285 82 d1-07 Frequency Reference 7 Frequency reference when digital inputs "Multi-Step Speed Reference 2, 3" (H1- = 4 and 5) are on. 0.00 Hz O 286 82 d1-08 Frequency Reference 8 Frequency reference when multi-function input "Multi-Step speed reference 1, 2, 3" (H1- = 3, 4, 5) are on.

0.00 Hz O 287 82 d1-17 Jog Frequency Reference Frequency reference when digital inputs "Jog Frequency Reference", "Forward Jog" or "Reverse Jog." are on. 6.00 Hz S 292 82 d2: Frequency Upper and Lower Limits Use d2 parameters to configure the frequency reference limits. d2-01 Frequency Reference Upper Limit Sets the frequency reference upper limit as a percentage of maximum output frequency (E1-04). Output speed is limited to this value even if the frequency reference is higher. This limit applies to all frequency reference sources. 0.0 to 110.0 100.0% O 289 83 d2-02 Frequency Reference Lower Limit Sets the frequency reference lower limit as a percentage of maximum output frequency (E1-04).

Output speed is limited to this value even if the frequency reference is lower. This limit applies to all frequency reference sources. 0.0 to 110.0 0.0% O 28A 83 d3: Jump Frequency Use d3 parameters to configure the drive Jump Frequency settings.