omron — Command Data

C.10 MEMOBUS/Modbus Data Table C.10 MEMOBUS/Modbus Data Table Table below lists all MEMOBUS/Modbus data. There are three types of data: command data, monitor data, and broadcast data. u Command Data It is possible to both read and write command data. Note: Bits that are not used should be set to 0. Refrain from writing to reserved registers. MEMOBUS/Modbus Communications C SIEP C710606 33A OYMC AC Drive – J1000 User Manual 199 Register No. Contents 0000H Reserved 0001H Operation Signals and Multi-function Inputs bit 0 H5-12 = 0: Forward Run Command (0 = Stop, 1 = Forward Run) H5-12 = 1: Run Command (0 = Stop, 1 = Run) bit 1 H5-12 = 0:

Reverse Run Command (0 = Stop, 1 = Reverse Run) H5-12 = 1: Forward/Reverse (0 = Forward, 1 = Reverse) bit 2 External Fault (EF0) bit 3 Fault Reset bit 4 Multi-Function Input 1 Function is ComRef when H1-01 = 40 (Forward/Stop). Refer to d: Reference Settings on page 82 for ComRef explanations. bit 5 Multi-Function Input 2 Function is ComCtrl when H1-02 = 41 (Reverse/Stop). Refer to d: Reference Settings on page 82 for ComCtrl explanations. bit 6 Multi-Function Input 3 bit 7 Multi-Function Input 4 bit 8 Multi-Function Input 5 bit 9 to F Reserved 0002H Frequency Reference Units are determined by parameter H5-13 (MEMOBUS frequency reference and frequency monitor unit).

0003H-0006H Reserved 0007H Analog Output Terminal AM Setting (10 V / 4000 H) 0008H Reserved 0009H Settings for Multi-Function Digital Outputs bit 0 Contact Output (terminal MA/MB-MC) bit 1 to F Reserved 000AH-000EH Reserved 000FH Control Selection Setting bit 0 to B Reserved bit C Enable Terminal S5 Input for Broadcast Data bit D to F Reserved