C.10 MEMOBUS/Modbus Data Table MEMOBUS/Modbus Communications C SIEP C710606 33A OYMC AC Drive – J1000 User Manual 201 Register No.

Contents 002BH Input Terminal Status bit 0 Terminal S1 Closed bit 1 Terminal S2 Closed bit 2 Terminal S3 Closed bit 3 Terminal S4 Closed bit 4 Terminal S5 Closed bit 5 to bit F Reserved 002CH Drive Status 2 bit 0 During Run bit 1 Zero Speed bit 2 Speed Agree bit 3 User Speed Agree bit 4 Frequency Detection 1 bit 5 Frequency Detection 2 bit 6 Drive Ready bit 7 During Undervoltage bit 8 During Baseblock bit 9 Frequency Reference from Operator Keypad bit A Run Command from Operator Keypad bit B Overtorque bit C, D Reserved bit E Fault bit F Communication Timeout 002DH Output Terminal Status bit 0 Multi-Function Contact Output (terminal MA/MB-MC) bit 1 to bit F Reserved 002EH to 0030H Reserved 0031H DC Bus Voltage, 1 Vdc units 0032H to 0033H Reserved 0034H Product Code 1 [ASCII], Product Type (J0 for J1000) 0035H to 003CH Reserved 003DH Communications Error Contents bit 0 CRC Error bit 1 Data Length Error bit 2 Reserved bit 3 Parity Error bit 4 Overrun Error bit 5 Framing Error bit 6 Timeout bit 7 to bit F Reserved 003EH Reserved 003FH Output Frequency 0.01% units 0040H to 007EH Used for various monitors U1-.

Refer to U: Monitors on page 181 for parameter details. 007FH Alarm Code, Refer to Alarm Register Contents on page 204 for alarm codes. 0080H to 0097H Used for monitors U2-. Refer to U: Monitors on page 181 for parameter details and Refer to Fault History Contents on page 203 for register value descriptions. 0098H High Word of Accumulated Operation Time Monitor (U4-01) 0099H Low Word of Accumulated Operation Time Monitor (U4-01) 009AH to 009BH Reserved 00ABH Drive Rated Current 00ACH to 00B5H Reserved 00B6H Frequency Reference After Soft-starter 0.01% units 00B7H Reserved 00B8H Frequency Reference 0.01% units 00B9H to 00BEH Reserved 00BFH oPE Error Number