4.3 The Drive and Programming Modes The following example is a continuation of the steps beginning on page 59 . Here, parameter C1-01 is accessed using the Verify Menu and is changed again to 20.0 s. To check the list of edited parameters: 5. Press the key to access the setting value. (number farthest to the left flashes) u Switching Between LOCAL and REMOTE Entering the run command using the LED operator is referred to as LOCAL, while entering the run command from an external device via the control circuit terminals or network option unit is referred to as REMOTE. WARNING! Sudden Movement Hazard.
The drive may start unexpectedly if the Run command is already applied when switching from LOCAL mode to REMOTE mode when b1-07 = 1, resulting in death or serious injury. Be sure all personnel are clear of rotating machinery and electrical connections prior to switching between LOCAL mode and REMOTE mode. There are two ways to switch between LOCAL and REMOTE. Note: 1. After selecting LOCAL, the LO/RE light will remain lit. 2. The drive will not allow the user to switch between LOCAL and REMOTE during run.
n Using the LO/RE Key on the LED Operator n Using Input Terminals S1 through S5 to Switch between LO/RE Switch between LOCAL and REMOTE using one of the digital input terminals S1 through S5 (set the corresponding parameter H1-01 through H1-05 to “1”). Follow the example below to set the digital input terminals. Note: 1. For a list of digital input selections, Refer to Parameter List on page 169 . 2. Setting a multi-function input terminal to a value of 1 disables the LO/RE key on the LED operator. u Parameters Available in the Setup Group n Setup Mode (STUP) Parameters used for this drive are classified into A to U.
To simplify the drive setup, frequently used parameters are selected and input into Setup Mode. 1. To set a parameter, the Setup Mode must be displayed first. Press the Up/Down key until is displayed. 2. Select the parameter and change the setting. Table 4.4 lists parameters available in the Setup group. If the desired parameter cannot be set in the Setup mode, use the Parameter Setting mode. Table 4.4 Setup Group Parameters 60 SIEP C710606 33A OYMC AC Drive – J1000 User Manual Step Display/Result 1. 2. Turn on the power to the drive. The initial display appears. 3. Press until the display shows the “Verify” representation.
Press to enter the list of parameters that have been edited from their original default settings. Scroll through the list by pressing the key. 4. Press the key until C1-01 appears. Step Display/Result 1. 2. Turn on the power to the drive. The initial display appears. Press . The LO/RE light will light up. The drive is now in Local. To set the drive for REMOTE operation, press the key again.
STOP Parameter Name b1-01 Frequency Reference Selection b1-02 Run Command Selection b1-03 Stop Method Selection C1-01 Acceleration Time 1 C1-02 Deceleration Time 1 Parameter Name C6-01 Duty Selection C6-02 Carrier Frequency Selection d1-01 Frequency Reference 1 d1-02 Frequency Reference 2 d1-03 Frequency Reference 3