omron — K6CM series Application Guide (EN)

K6CM Target Application Homogenizers Material (liquid/powder) Facility details Pulley Device that mixes and stirs a liquid (such as milk) into a consistent emulsion so it does not separate. V-belt Piston pump Sliding Motor operation conditions 90kW/200V Driving the motor by direct connection to commercial power supply: 50Hz Failure mode Load abnormality (Piston rubber gasket deterioration) Material (liquid/powder) Homogenization equipment Detection parameters Degradation level 1 Stirring system Degradation level 1 measurement results obtained from K6CM-CI  Moving Average Times: 0 Moving Average Times: 32 1. Value for a normal working motor:

74 New Rubber Gasket 100 95 85 90 Degradation level 80 2. Value for motor whose operation requires caution: 79 Rubber Gasket should be replaced 75 70 65 3. Value for motor not working normally: 84 Rubber Gasket is damaged 50 60 55 0 2 4 6 8 10 0 2 4 6 8 10 12 14 0 2 4 6 8 Measurement time (minutes) Alarm threshold degradation level 1 for this application (examples) Alarm threshold (Warning) 77 Enables early detection of facility anomalies to reduce production loss. Expected implementation effects Alarm threshold (Critical) 85 Improves production quality by detecting facility anomalies. 20 IV .

Stirring system application Comprehensive current diagnosis type rmal Wa rning Crit ical Degradatio n level average n level average Degradatio n level average 8 4 75 7 9 bber Gasket 2. Rubb er Gasket 3. Rubb er Gasket should b e replaced is da maged