Num Length Object name Description This object is use to switch all of the selected relays on /off. Note: The object is valid only when the following requirements are met. 48 [Central Function] 1 bit | All Relays On/Off The chart shows the dynamic range for this parameter: 7 Se we Description Output mode (1)The parameter "All Relays On/Off" and "Relay n(n=1~4) control"in "General setting” are checked On delay (2)When "Relay n (n=1~4) 49 [Central Function] All Relays On/Off (Status) 1 bit control" is checked, there is a submenu called "Relays” in which the parameter "Central function” shall be checked Sends the on/off status for the relays. 1: all of the selected relays are off. 0:
one of the selected relays is on. 4.1.3.1 Relays enable-Relays Once a relay is activated, a new page of Relays will appear. At this subpage, the further parameterization can be done. The following illustration shows the setting options at the submenu for a relay Dynamic range Off delay .
Central function — Custom description Relay, maximum allowed of 30 bytes @ normally opened | Defines the default behavior @ normally closed | of the relay @ 0~65535s 0 [Os] Adjustment of the time at which the switch-on process shall be delayed @ 0~65535s [0s] Adjustment of the time at which the switch-off process shall be delayed @ no check @ check © normally opened On delay 0 Sends status signals from @ at change the object "Relays On/Off" @ always atinput | with the option you selected of telegram status Send status Send status cyclic | @0~65535s (0=not active) [0s] Off delay 0 Central function v Send status at change Send status cyclic(0=not active) 0 normally closed ~ Seconds a Seconds Additional inverted status no change Behavior at unlocking no change Priority/Forced control not active Behavior after KNX Bus power up no change Behavior after KNX Bus power down no change Behavior after AC power on previous status @ no check @ check Sends status signals from the object "Relays On/Off"at intervals you desire.
If actives, inverter signals received from the object "On/ Off(Inverted Status)", that is 1-0; 0-1 * Seconds Additional inverted status Behavior at locking Whether it is controllable via J the object "[Central Function] All Relays On/Off" @ no send,passive Description Output mode Comment [default value] Behavior at locki ocking @ on © off @ no change Sets the action to be performed when a lock order is received. - Priority: _ Note: Priority: Lock > Priority /Force control 19 20