3.4 Wiring 3.3 Electrical Configuration DALI end e The maximum number of ECGs connected is 64 per bus. e The maximum e Use wires with an adequate cross-section. e Use suitable mounting tools to do the wiring. length is 300m (with a cable cross-section of 1.5 Type mm?) KNX end e The maximum Solid wire number of bus devices connected is 256. e The maximum length ofa line segment is 350 m, measured along the line between the power supply and the furthest bus device. e The maximum distance between two bus devices cannot exceed 700m.
e The maximum length ofa bus line is 1000 m, keeping into account allsegments AC and relay terminals L,N,K1,K2,K3,K4 0.5 ~4.0mm Stranded DALI terminals KNX bus terminal (DALI-A, DALI-B) | (KNX) 0.5~1.45mm ; 0.6~0.80 ; —---- 0.5~2.5mm 0.5~1.5mm wire gauge 12 ~ 26AWG 16 ~ 26AWG 20 ~ 22AWG Wire stripping 5 wire American 7 ~ 8mm 7 ~ 8mm length (0.276"~ 0.315") | (0.276"~ 0.315") | Screwdriver 3mm Slotted 3mmSlotted =| ------ Recommended tightening torque 5 kgf-cm (4.4|lb-in) | 5kgf-cm (4.4Ib-in)| ------ > 0.196" (0-19) 3.5 ETS App (DCA) KNX system Vv LED Driver(A1) DA DA The application for the gateway is based on the standard interface for the configuration of communication objects and parameters as well as aspecial surface for configuring the DALI bus systems.
This special interface is designed as a DCA (Device Control App) for the ETS. All required program data is automatically created when the App is imported. DCA App installation steps are as follows: (1)Click the "Settings" button in the upper right corner of ETS, select "ETS Apps", and then select "+Install App". LED Driver(A2) DA DA LED Driver(A64) DA DA