Lynx Smart BMS Alarms: Alarms indicate the reason why the system is shutdown. Error codes Alarm codes Lynx Distributor related Page 42 Appendix VictronConnect warning code Message Instructions / remarks W-D08 Communication with distributor H lost Check the cable between BMS and Distributor. VictronConnect alarm code Message Instructions / remarks A-B01 Low cell voltage Charge battery. The system will turn the loads back on when the battery is sufficiently charged. A-B02 High current Reduce charging current or turn off some loads. The system will try to re-enable chargers or loads in 5 minutes.
A-B06 Load disconnected The loads have been turned off via the ATD contact and/or via the GX device. Resolve this alarm by charging the battery. If not resolved, eventually the contactor will open and the DC system will be disconnected. A-B07 Low SoC Charge battery. The system will turn the loads back on when the battery is sufficiently charged. VictronConnect error code Message Instructions / remarks E-B01 Battery init failure Check that all batteries are properly connected. E-B02 No battery found Verify that the BMS cable loop is closed. E-B05 Invalid number of batteries Check that all batteries are properly connected.
E-B09 Battery voltage not allowed The battery voltage is too high or too low. Check the battery voltage and check the battery settings in the VictronConnect app. This error occurs when the battery voltage is outside all system voltage ranges (9V > Vbat > 60V) E-B11 Hardware error Contact your Victron dealer. E-B25 Pre-charge error The load resistance is too low to pre-charge the loads. Disconnect or reduce some DC loads. E-B26 Contactor error Contact your Victron dealer. E-B32 BMS cable error Check the battery M8 cabling. E-B34 Wrong system voltage Check battery voltage settings in the VictronConnect app. E-B35 Pre-charge timeout The load capacity is too high to pre-charge.
Disconnect some DC loads. E-B36 ATC/ATD failure Check ATC/ATD wiring and make sure that all loads and chargers are controlled by ATC or ATD. E-B116 Calibration data lost Contact your Victron dealer. E-B119 Settings data lost Settings data is corrupt. Go to the settings page and reset to defaults. VictronConnect alarm code Message Instruction / remarks A-F01 Fuse "Fuse 1" is blown _ Check your system and replace fuse. A-F02 Fuse "Fuse 2" is blown _ A-F03 Fuse "Fuse 3" is blown _ A-F04 Fuse "Fuse 4" is blown _