1. SAFETY INSTRUCTIONS In general SAVE THESE INSTRUCTIONS Please read the documentation supplied with this product first, so that you are familiar with the safety signs en directions before using the product. This product is designed and tested in accordance with international standards. The equipment should be used for the designated application only. WARNING: DANGER OF ELECTRICAL SHOCK The product is used in combination with a permanent energy source (battery). Even if the equipment is switched off, a dangerous electrical voltage can occur at the input and/or output terminals. Always switch the AC power off and disconnect the battery before performing maintenance.

In addition discharge the battery terminals or wait 30 minutes. This appliance is not designed for use by young children or people who cannot read or understand the manual unless they are under the supervision of a responsible person to ensure that they can use the battery charger safely. Store and use the battery charger out of the reach of children, and ensure that children cannot play with the charger. The product contains no internal user-serviceable parts. Do not remove the front panel and do not put the product into operation unless all panels are fitted. All maintenance should be performed by qualified personnel. Never use the product at sites where gas or dust explosions could occur.

Refer to the specifications provided by the manufacturer of the battery to ensure that the battery is suitable for use with this product. The battery manufacturer's safety instructions should always be observed. WARNING: do not lift heavy objects unassisted. WARNING – RISK OF EXPLOSIVE GASES. i. WORKING IN VICINITY OF A LEAD-ACID BATTERY IS DANGEROUS. BATTERIES GENERATE EXPLOSIVE GASES DURING NORMAL BATTERY OPERATION. FOR THIS REASON, IT IS OF UTMOST IMPORTANCE THAT EACH TIME BEFORE SERVICING THE UNIT IN THE VICINITY OF THE BATTERY, YOU READ THIS MANUAL AND FOLLOW THE INSTRUCTIONS EXACTLY. ii.

To reduce risk of battery explosion, follow these instructions and those published by battery manufacturer and manufacturer of any unit you intend to use in vicinity of battery. Review cautionary marking on these products and on engine Personal Precautions: i. Someone should be within range of your voice or close enough to come to your aid when you work near a lead-acid battery. ii. Have plenty of fresh water and soap nearby in case battery acid contacts skin, clothing, or eyes iii. Wear complete eye protection and clothing protection. Avoid touching eyes while working near battery. iv. If battery acid contacts skin or clothing, wash immediately with soap and water.

If acid enters eye, immediately flood eye with running cold water for at least 10 min and get medical attention immediately. v. NEVER smoke or allow a spark or flame in vicinity of battery or engine. vi. Be extra cautious to reduce the risk of dropping a metal tool onto battery. It might spark or short-circuit battery or other electrical part that may cause explosion. vii. Remove personal metal items such as rings, bracelets, necklaces, and watches when working with a lead- acid battery. A lead-acid battery can produce a short circuit current high enough to weld a ring or the like to metal, causing a severe burn. viii. NEVER charge a frozen battery. ix.

If necessary to remove battery from vessel, always remove grounded terminal from battery first. Make sure all accessories in the vessels are off, so as not to cause an arc. x. Be sure the area around the battery is well ventilated. xi. Clean battery terminals. Be careful to keep corrosion from coming in contact with eyes. xii. Study all battery manufacturer's specific precautions such as removing or not removing cell caps while charging and recommended rates of charge. xiii. Add distilled water in each cell until battery acid reaches level specified by battery manufacturer. This helps purge excessive gas from cells. Do not overfill.

For a battery without cell caps, carefully follow manufacturer's recharging instructions. Installation Read the installation instructions before commencing installation activities. For electrical work, follow the local national wiring standard, regulation and this installation instructions. This product is a safety class I device (supplied with a ground terminal for safety purposes). Its AC input and/or output terminals must be provided with uninterruptable grounding for safety purposes. An additional grounding point is located on the outside of the product.

If it can be assumed that the grounding protection is damaged, the product should be taken out of operation and prevented from accidentally being put into operation again; contact qualified maintenance personnel. 1

Стр. 3

Ensure that the connection cables are provided with fuses and circuit breakers. Never replace a protective device by a component of a different type. Refer to the manual for the correct part. Check before switching the device on whether the available voltage source conforms to the configuration settings of the product as described in the manual. Ensure that the equipment is used under the correct operating conditions. Never operate it in a wet or dusty environment. Ensure that there is always sufficient free space around the product for ventilation, and that ventilation openings are not blocked. Install the product in a heatproof environment.

Ensure therefore that there are no chemicals, plastic parts, curtains or other textiles, etc. in the immediate vicinity of the equipment. Transport and storage On storage or transport of the product, ensure that the mains supply and battery leads are disconnected. No liability can be accepted for damage in transit if the equipment is not transported in its original packaging. Store the product in a dry environment; the storage temperature should range from -20 °C to +60 °C. Refer to the battery manufacturer's manual for information on transport, storage, charging, recharging and disposal of the battery. 2

Стр. 4

2. DESCRIPTION 2.1 In general The basis of the Quattro is an extremely powerful sine inverter, battery charger and automatic switch in a compact casing. The Quattro features the following additional, often unique characteristics: Two AC inputs; integrated switch-over system between shore voltage and generating set The Quattro features two AC inputs (AC-in-1 and AC-in-2) for connecting two independent voltage sources. For example, two generator sets, or a mains supply and a generator set. The Quattro automatically selects the input where voltage is present. If voltage is present on both inputs, the Quattro selects the AC-in-1 input, to which the generating set is normally connected.

Two AC outputs Besides the usual uninterruptable output (AC-out-1), an auxiliary output (AC-out-2) is available that disconnects its load in the event of battery operation. Example: an electric boiler that is allowed to operate only if the genset is running or shore power is available. Automatic and uninterruptible switching* In the event of a supply failure or when the genset is switched off, the Quattro will switch over to inverter operation and take over the supply of the connected devices. This is done so quickly that operation of computers and other electronic devices is not disturbed (Uninterruptible Power Supply or UPS functionality).

This makes the Quattro highly suitable as an emergency power system in industrial and telecommunication applications. Virtually unlimited power thanks to parallel operation Up to 4 Quattros can operate in parallel. Four 48/15000/200 units, for example, will provide 48 kW / 60 kVA output power and 800 Amps charging capacity. Three phase capability Three units can be configured for three-phase output. But that’s not all: up to 6 sets of three units can be parallel connected to provide 144 kW / 180 kVA inverter power and more than 2400 A charging capacity. PowerControl – maximum use of limited shore current The Quattro can supply a huge charging current.

This implies heavy loading of the shore connection or generating set. For both AC inputs, therefore, a maximum current can be set. The Quattro then considers other power users, and only uses 'surplus' current for charging purposes. - Input AC-in-1, to which usually a generating set is connected, can be set to a fixed maximum with DIP switches, with VE.Net or with a PC, so that the generating set is never overloaded. - Input AC-in-2 can also be set to a fixed maximum. In mobile applications (ships, vehicles), however, a variable setting by means of a Multi Control Panel will usually be selected.

In this way the maximum current can be adapted to the available shore current in an extremely simple manner. PowerAssist – Extended use of your generating set and shore current: the Quattro “co-supply” feature The Quattro operates in parallel with the generating set or the shore connection. A current shortfall is automatically compensated: the Quattro draws extra power from the battery and helps along. A current surplus is used to recharge the battery. Three programmable relays The Quattro is equipped with 3 programmable relays. The relays can be programmed for all kinds of other applications however, for example as a starter relay for a generating set.

Two programmable analogue/digital input/output ports The Quattro is equipped with 2 analogue/digital input/output ports. These ports can be used for several purposes. One application is communication with the BMS of a lithium-ion battery. Frequency shift When solar inverters are connected to the output of a Quattro, the excess solar energy is used to recharge the batteries. Once the absorption voltage is reached, the Quattro will shut down the solar inverter by shifting the output frequency to 1 Hz (from 50 Hz to 51 Hz, for example). Once the battery voltage has dropped slightly, the frequency returns to normal, and the solar inverters will restart.

Built-in Battery Monitor (optional) The ideal solution is when Quattros are part of a hybrid system (diesel generator, inverter/chargers, storage battery, and alternative energy). The built-in battery monitor can be set to start and stop the generator: - start at a preset % discharge level, and/or - start (with a preset delay) at a preset battery voltage, and/or - start (with a preset delay) at a preset load level. - Stop at a preset battery voltage, or - stop (with a preset delay) after the bulk charge phase has been completed, and/or - stop (with a preset delay) at a preset load level. * Not evaluated for UL 1741 3

Стр. 5

Solar energy The Quattro is extremely suitable for solar energy applications. It can be used for building autonomous systems as well as mains-coupled systems. Emergency power or autonomous operation on mains failure Houses or buildings provided with solar panels or a combined micro-scale heating and power plant (a power-generating central heating boiler) or other sustainable energy sources have a potential autonomous energy supply which can be used for powering essential equipment (central heating pumps, refrigerators, deep freeze units, Internet connections, etc.) during a power failure.

A problem in this regard, however, is that mains-coupled solar panels and/or micro-scale heating and power plants drop out as soon as the mains supply fails. With a Quattro and batteries, this problem can be solved in a simple manner: the Quattro can replace the mains supply during a power failure. When sustainable energy sources produce more power than necessary, the Quattro will use the surplus to charge the batteries; in the event of a shortfall, the Quattro will supply additional power from its battery energy resources. Programmable with DIP switches, VE.Net panel or personal computer The Quattro is supplied and ready for use.

Three features are available for changing certain settings if desired: - The most important settings (including parallel operation of up to three devices and 3-phase operation) can be changed in a very simple manner using Quattro DIP switches. - All settings can be changed with a PC and free-of-charge software, downloadable from our website, www.victronenergy.com . 2.2 Battery charger Adaptive 4-stage charging characteristics: bulk – absorption – float – storage The microprocessor-driven adaptive battery management system can be adjusted for various types of batteries. The adaptive function automatically adapts the charging process to battery use. The right amount of charge:

variable absorption time In the event of slight battery discharge, absorption is kept short to prevent overcharging and excessive gas formation. After deep discharging, the absorption time is automatically extended in order to fully charge the battery. Preventing damage due to excessive gassing: the BatterySafe mode If, in order to quickly charge a battery, a high charge current in combination with a high absorption voltage has been chosen, damage due to excessive gassing will be prevented by automatically limiting the rate of voltage increase once the gassing voltage has been reached. Less maintenance and ageing when the battery is not in use:

the storage mode The Storage mode kicks in whenever the battery has not been subjected to discharge during 24 hours. In the Storage mode float voltage is reduced to 2,2 V/cell (52,8 V for 48 V battery) to minimise gassing and corrosion of the positive plates. Once a week the voltage is raised back to the absorption level to “equalize” the battery. This feature prevents stratification of the electrolyte and sulphation, a major cause of early battery failure. Increasing service life of the battery: temperature compensation The temperature sensor (supplied with the product) serves to reduce charging voltage when the battery temperature rises.

This is particularly important for maintenance-free batteries, which could otherwise dry out by overcharging. Battery voltage sense: the correct charge voltage Voltage loss due to cable resistance can be compensated by using the voltage sense facility to measure voltage directly on the DC bus or on the battery terminals. More on batteries and charging Our book “Energy Unlimited” offers further information on batteries and battery charging and is available free of charge on our website (see www.victronenergy.com -> Support & Downloads -> General Technical Information). For more information on adaptive charging, please also refer to the General Technical Information on our website.

2.3 Self-consumption solar energy storage systems (ESS)* When the Quattro is used in a configuration that will feed back energy to the grid, it is required to enable grid-code compliance by selecting the grid code country setting with the VEConfigure tool to comply with the local rules. Once set, a password will be required to disable grid code compliance or change grid-code-related parameters. If the Quattro does not support the local grid code, an external certified interface device should be used to connect the Quattro to the grid.

The Quattro can also be used as a bidirectional inverter operating parallel to the grid, controlled by an external source, and integrated into an energy storage system (ESS). For more information on ESS, see: https://www.victronenergy.com/media/pg/Energy_Storage_System/en/index-en.html * Not evaluated for UL 1741 4