Danfoss — mg20b602.pm6 (EN)

VLT ® 2000 Series How to size your VLT I Dimensions (cont’d) VLT 2020-2060 three-phase, 380-415/460 V VLT 2040-2050 three-phase, 208-240 V Min. space over and under frequency converters: 100 mm. Min. space to the left and the right of frequency converters: 0 mm (side-by-side mounting) VLT 2020-2060 with module three-phase, 380-415/460 V with 100 mm module: A = 462 mm a = 437 mm With 170 mm module: A = 532 mm a = 507 mm Min. space over and under frequency converters: 100 mm. Min. space to the left and the right of frequency converters: 0 mm (side-by-side mounting) 36 MG.20.B6.02 – VLT is a registered Danfoss trademark