Danfoss — mg20b602.pm6 (EN)

VLT ® 2000 Series Installation I Before you start Read the safety rules on page page page page page 4 before you start. I Mechanical installation Item 1 Drilling template (enclosed in box) For sizing and drilling of holes you can use the enclosed Drilling Template. That I have done Ensure min. 100 mm (10 cm) free air space above and below the VLT frequency converter. This also applies when a module has been mounted. Make sure that the ambient temperature does not exceed 40°C. Item 2 Side by side mounting VLT frequency converters can be mounted side by side, without any space between them.

Item 3 Module If you want to use a module (to be placed underneath) you must take the physical dimensions into account. I Electrical installation Item 1 Prefuses Choose the right prefuses: That I have done Mains supply 1 x 220/230/240 V Mains supply 3 x 380-460 V 3 x 208/220/230/240 V VLT 2010 Max. 10A VLT 2015 Max. 16 A VLT 2020 Max. 20 A VLT 2030 Max. 20 A VLT 2040 Max. 20 A VLT 2050 Max. 25 A VLT 2020 Max. 16 A VLT 2025 Max. 16 A VLT 2030 Max. 16 A VLT 2040 Max. 16 A VLT 2050 Max. 16 A VLT 2060 Max. 20 A See Special conditions: Cut-in current 6 MG.20.B6.02 – VLT is a registered Danfoss trademark