Монтаж VLT ® AQUA Drive, габарит корпуса D Инструкция по эксплуатации 230 VAC 50/60Hz TB5 R1 130BC548 11 TB6 Contactor Anti-condensation heater (optional) (optional) 2 2 230 VAC 50/60Hz 3 Phase power input 91 (L1) 92 (L2) 93 (L3) PE = = = (U) 96 (V) 97 (W) 98 (PE) 99 95 Load Share Switch Mode Power Supply 88 (-) 89 (+) Motor 15mA 200mA 10Vdc 24Vdc Regen + (R+) 82 Brake resistor Regen +10Vdc 50 (+10 V OUT) A53 U-I (S201) (R-) 81 + - + - Regen - 83 0 VDC - 10VDC 0/4-20 mA 53 (A IN) A54 U-I (S202) ON=0-20mA OFF=0-10V Relay1 03 400Vac, 2A 0 VDC - 10VDC 0/4-20 mA 54 (A IN) 2 1 ON 02 240Vac, 2A 55 (COM A IN) Relay2 01 12 (+24V OUT) 06 240Vac, 2A 13 (+24V OUT) 18 (D IN) 400Vac, 2A P 5-00 24V (NPN) 0V (PNP) 05 04 0V (PNP) 24V (NPN) 19 (D IN) (COM A OUT) 39 Analog Output 20 (COM D IN) S801/Bus Term.
OFF-ON (A OUT) 42 0/4-20 mA 24V (NPN) 0V (PNP) 27 24V (D IN/OUT) ON=Terminated OFF=Open 0V 5V 1 2 Brake Temp (NC) 24V 29 0V (PNP) 24V (NPN) (D IN/OUT) S801 0V 0V 0V (PNP) 24V (NPN) RS-485 RS-485 Interface (P RS-485) 68 32 (D IN) 24V (NPN) 0V (PNP) (COM RS-485) 61 (N RS-485) 69 33 (D IN) (NPN) = Sink (PNP) = Source 37 (D IN) - option Рисунок 2.2 Схема межкомпонентных подключений 12 MG21A250 - VLT ® является зарегистрированным товарным знаком компании Danfoss 1 2 ON 1 2 ON