Delta — Load Cell Module DVP02LC-SL — Operation Manual by Delta Electronics (EN)

Load Cell Module DVP02LC-SL „ Gross/Net: Corresponds to the value in CR#7. Scroll down to select displaying the gross weight or net weight. „ Tare weight: Corresponds to the value in CR#8 and CR#9. Enter the tare weight here, or click “Read TW” to set it up. The range is -32,768 to 32,767, and the default setting is 0. „ Read TW: Corresponds to the value in CR#6. Click “Read TW” to take the average value of each channel as the tare weight. „ Average times: Corresponds to the value in CR#10 and CR#11. The range is 1 to 100, and the default setting is „ Maximum weight: 10. Corresponds to the value in CR#35 and CR#36. Enter the maximum weight here.

When the measured value exceeds this weight, an error status will be displayed. The range is -32,768 to 32,767, and the default setting is 32,767. „ Unit of measurement: Corresponds to CR#22 and CR#23 for CH1 and CR#24 and CR#25 for CH2. You can enter a unit here for the user’s reference. Maximum 4 characters are allowed in this column. The default setting is Kg. „ Standstill times: The times of standstill checks, corresponding to the value in CR#16 and CR#17. Enter the times here. The range is 1 to 500, and the default setting is 5. „ Standstill range: The range for standstill check, corresponding to the value in CR#18 and CR#19. Enter the range (1 to 10,000) here.

The default setting is 10. „ Zero band: The upper and lower limits for the zero point check. The upper limit for CH1 corresponds to the value in CR#37, and the lower limit corresponds to the value in CR#39. The upper limit for CH2 corresponds to the value in CR#38, and the lower limit corresponds to the value in CR#40. When the weight measured is within the range, the status code will be set to “ zero bit " indicating that it is currently in empty status now. Enter the upper and lower limits here. The range is K-32,768 to K32,767, and the default setting is -10 to 10. „ Filter ratio setting The filter percentage, corresponding to the value in CR#43 and CR#44. The range is 1 to 5.

The average weight after being filtered will be displayed as the filter average values for CH1 and CH2 on the toolbar, or you can check CR#45 and CR#46 for the filter average value. The default setting is 2. DVP-PLC Operation Manual 24