Load Cell Module DVP02LC-SL 6.5 Status Settings In the status setting window, you can view the measuring results and the operation status of DVP02LC-SL, including the present average value in CH1 and CH2, the unit of measurement, status codes and error codes. „ Average value: The average weights at CH1 and CH2, corresponding to the values in CR#12 and CR#13. The unit after the figure is the previously set unit for measurement. „ Status code: Corresponds to the value set in CR#50, indicating the measuring statuses at CH1 and CH2, including the empty load, overload and whether the measured values are stable. y CH1 zero weight (empty): Corresponds to bit0 of CR#50.
When the value measured at CH1 equals 0, the indicator will turn red. y CH1 max. weight (overload): Corresponds to bit2 of CR#50. When the value measured at CH1 exceeds the maximum weight set, the indicator will turn red. DVP-PLC Operation Manual 26